Description for Barber Colman VB-7222-0-4-2
VB-7222 series single seat, stem up closed, two-way valves control water from 20 to 281F (-7 to 138C) or steam to 281F (138C) maximum in heating or air conditioning systems. They are used for two-position or proportional control applications. Valve assemblies require an actuator and a valve linkage that must be purchased separately.Features
5/8' O.D., 45 SAE flared end fittings. Equal percentage flow characteristics for twoposition or proportional control of water or steam. 250 psig pressure rating per ANSI Standards (B16.15-1985) for cast bronze bodies. Spring-loaded TFE packing.